Model: RY-ELE HDR-100-24
Output: 24V DC, 3.83A Rated Current (100W Max Output Power)
Input Voltage Range: 85–264VAC (277VAC operational) / 120–370VDC
Form Factor: 70mm Width (Compact Step Shape Plastic Housing)
Efficiency: Up to 89% (Typical at 230VAC)
Mounting: TS-35/7.5 or TS-35/15 DIN Rails
HDR-100-24 100W 24VDC 2.5A Ultra Slim DIN Rail Power Supply
Output: 24V 3.83A (100W)
Input: 85-264VAC (277VAC available) / 120-370VDC
Efficiency: 89% (Typical)
Ripple & Noise: <150mV
Operating Temp: -30°C to +70°C (with derating)
Protection: Overload & Short-circuit (Hiccup mode, Auto-recovery)
Withstand Voltage: 4KVAC Input-to-Output
Mounting: DIN Rail Mountable (Dimensions: 70×90×54.5 mm)
Input
Voltage Range: 85~264VAC (277VAC available), 47Hz~63Hz (120~370VDC, 390VDC available)
Working Current: 3A at 115VAC / 1.6A at 230VAC
Inrush Current: Cold start 35A at 115VAC / 70A at 230VAC
Output
Rated Voltage: 24V
Rated Current: 3.83A
Rated Power: 100W
Voltage Accuracy: ±1.0% (12V model: ±2.0%)
Voltage Adjustment Range: 24~25.5V (Standard model)
Load Regulation: ±1.0%
Line Regulation: ±1.0%
Startup, Rise, Hold-up Time: 500ms, 60ms at 230VAC/115VAC; Hold-up time: 30ms at 230VAC, 12ms at 115VAC
Protection & Environment
Overload Protection: 0% (rated output power); Output voltage <50% enters Hiccup mode, 50%~100% enters Constant Current mode. Auto-recovery after fault removal.
Short Circuit Protection: Overload/Overvoltage protection, Hiccup mode, Auto-recovery.
Operating Temp & Humidity: -30℃~+70℃ (Refer to derating curve); 20%~90% RH, non-condensing.
Storage Temp & Humidity: -40℃~+85℃; 10%~95% RH, non-condensing.
Withstand Voltage: Input-Output: 4KVAC for 1 minute.
Isolation Resistance: Input-Output: 100MΩ/500VDC/25℃/70%RH.
Dimensions & Weight
Dimensions: 70×90×54.5 mm (W×H×D)
Net Weight: 0.27Kg / unit
Application Scenario
FAQ